Hot or cold water circulation pump with in-line ports, suitable for installation directly on the pipework of civil and industrial heating, air conditioning, refrigeration, and sanitary water systems
Liquid Type: from 2 to 67 m3/h with head up to 13,7 metres.
Uses: from 2 to 67 m3/h with head up to 13,7 metres.
Applications: Clean, free from solids or abrasive substances, not viscous, not aggressive, not crystallised, chemically neutral
Typology:
Family: Pump body and motor support in cast iron. PN10 flanged connections with threaded holes for control pressure gauges. Technopolymer impeller and carbon/ceramic mechanical seal. Four-pole, asynchronous motor for the KLM and DKLM versions and two-pole for the KLP and DKLP versions. Built-in thermal and current overload protection and a capacitor permanently on in the single- phase version. Three-phase motors should be protected with a suitable overload protection complying with the regulations in force. In the twin version there is a built-in automatic clapet valve on the delivery vent; the standard supply also includes a blank flange.
Application Limit: Operating range: from 2 to 67 m3/h with head up to 13.7 metres. Liquid temperature range: from -15°C to +120°C. Pumped liquid characteristics:clean, free from solids or abrasive substances, not viscous, not aggressive, not crystallised, chemically neutral. Maximum ambient temperature: +40°C Maximum working pressure: 10 bar (1000 kPa). Protection level: IP 55 Insulation class: F Standard flanging: PN 10/PN 6 Counter flanges either threaded or with welded collar as requested.